The APA's recent proposal (RB164) to expand the use of the
narrow wall bracing method was defeated at the International
Code Council's Final Action Hearings held in Detroit, September
28 - October 2, 2005. Several industry leaders, including
Simpson Strong-Tie, presented compelling test evidence that
impacted the outcome of the vote.
In the 2004 Supplement to the International Residential Code
(IRC), narrow braced walls are permitted in limited applications.
In 2005, the APA attempted to expand this application to include
higher seismic zones, second-story applications and usage away
from corners. However, test results completed by Simpson and
Washington State University (WSU) indicated there were
significant performance issues that need to be addressed.
Test Results Completed by Simpson Strong-Tie and Washington State University
Prior to the ICC Final Action Hearings, Simpson initiated a
comprehensive testing program to understand the performance
of narrow wall systems and see if the APA test results could be
replicated. There were a number of concerns with the proposed code change. The testing focused on three main issues:
- The Use of Gypsum
Although the use of gypsum is required by the code, APA's
in-house tests did not include gypsum. The Simpson testing
used gypsum on the interior of the APA narrow wall and
compared it to a standard, code-accepted benchmark wall.
Simpson’s testing indicated that the APA wall performed
approximately 20% below the benchmark wall when both walls
were constructed per code.
- Common Installation Errors
In APA's test report covering common installation errors, the
tested walls used a 15,000 lb. ultimate capacity holdown. This
holdown is not listed as a requirement in APA's specifications.
Therefore, Simpson completed testing without the use of this
holdown device to simulate the condition where no uplift
restraint is provided by the return wall because of wind loads
acting on the return wall. Common installation errors, such as
missing nails were tested, which decreased the wall's
performance dramatically. Changing the nail spacing from 3" on
center to 4" on center, for example, resulted in an approximate
50% reduction in performance. - Load Capacity
After repeated testing and modifications to test set-ups to
address issues such as load beam stiffness and holdown bolt
tension, Simpson was unable to replicate the loads published by
the APA. Although variations in results are expected in this type
of testing, Simpson consistently achieved load capacities well
below those stated by the APA. It was then that Simpson asked
WSU to perform a similar independent research and testing
program.
WSU tested the narrow walls and code-accepted benchmark
walls. At design levels, the WSU testing indicated:
- The narrow walls performed significantly below the code accepted benchmark walls (36% below).
- The WSU test results of the narrow wall performance were 36% to 54% below APA's results.
ICC Hearings and Next Steps
Simpson and WSU test results were presented at the ICC
Hearings this fall. The proposal to expand the use of the narrow
wall bracing method, RB164 was voted down and denied
approval.
In an effort to clarify the bracing provisions outlined in the IRC,
a task group of industry leaders has been assembled and will
meet in January 2006. The goals of the task group include:
- Re-organizing and simplifying the wall bracing provisions
of the code (a non-technical rewrite);
- Developing additional standards for testing and evaluating
existing and new bracing methods;
- Researching the effects of combining various wall bracing
systems;
top
|
|
|
 |
 |