AT High-Strength Anchoring Adhesive

Tension and Shear Loads for Threaded Rod Anchors

in 6 and 8-Inch Normal-Weight
Grout-Filled CMU

On This Page:

 
 
Tension Load Shear Load Threaded Rod Concrete Block (CMU)
Tension and Shear Loads for Threaded Rod Anchors in 6 and 8-Inch Normal-Weight Grout-Filled CMU
Tension and Shear Loads for Threaded Rod Anchors in 6 and 8-Inch Normal-Weight Grout-Filled CMU
  1. Threaded rods must comply with ASTM F1554 Grade 36 minimum.
  2. Values for 6- and 8-inch wide concrete masonry units (CMU) with a minimum specified compressive strength of masonry, f'm, at 28 days is 1500 psi.
  3. Embedment depth is measured from the outside face of the concrete masonry unit for installations through a face shell.
  4. Allowable loads may be increased 33 1/3% for short-term loading due to wind or seismic forces where permitted by code.
  5. Refer to in-service temperature sensitivity chart for allowable load adjustment for temperature.
  6. The tabulated allowable loads are based on a safety factor of 5.0 for installations under the IBC and IRC.
  7. Anchors must be spaced a minimum distance of four times the anchor embedment.

 

Figure 1: Allowable anchor placement in grouted CMU face shell
allowable anchor placement in grouted cmu face shell
Figure 2: Anchor placement in grouted CMU mortar "T" joint
anchor placement in grouted cmu mortar 't' joint


Tension Load Shear Load Threaded Rod Concrete Block (CMU)
Tension and Shear Loads for Threaded Rod Anchors in 6 and 8-Inch Normal-Weight Grout-Filled CMU
Tension and Shear Loads for Threaded Rod Anchors in 6 and 8-Inch Normal-Weight Grout-Filled CMU
 
  1. Threaded rods must comply with ASTM F1554 Grade 36 minimum.
  2. Values for 6- and 8-inch wide concrete masonry units (CMU) with a minimum specified compressive strength of masonry, f'm, at 28 days is 1500 psi.
  3. Embedment depth is measured from the outside face of the concrete masonry unit for installations through a face shell.
  4. Allowable loads may be increased 33 1/3% for short-term loading due to wind or seismic forces where permitted by code.
  5. Refer to in-service temperature sensitivity chart for allowable load adjustment for temperature.
  6. The tabulated allowable loads are based on a safety factor of 5.0 for installations under the IBC and IRC.
  7. Anchors must be spaced a minimum distance of four times the anchor embedment.
  8. Shear load applied perpendicular to edge of CMU wall.
  9. Shear load applied parallel to edge of CMU wall.
Figure 3: Anchor installed in cell opening (top of wall)
Anchor installed in cell opening
 