How to use these charts:
- The following tables are for reduced edge distance.
- Locate the anchor size to be used for either a tension and/or shear load application.
- Locate the embedment (E) at which the anchor is to be installed.
- Locate the edge distance (Cact) at which the anchor is to be installed.
- The load-adjustment factor (fc) is the intersection of the row and column.
- Multiply the allowable load by the applicable load-adjustment factor.
- Reduction factors for multiple edges are multiplied together.
- Adjustment factors do not apply to allowable steel strength values.
- Adjustment factors are to be applied to allowable Shear Load Based on Concrete Edge Distance values only.