Blue Banger Hanger® Cast-In-Place, Internally-Threaded Inserts
Tension and Shear Loads
in Normal-Weight or Sand-Lightweight Concrete over Metal Deck
Metal Deck Insert: Tension Loads in Normal-Weight or Sand-Lightweight Concrete
over Metal Deck
- Allowable load must be the lesser of the concrete or rod strength.
- The allowable loads based on concrete strength are based on a factor of safety of 4.0.
- Allowable loads may not be increased for short-term loading due to wind or seismic forces.
- Anchors may be installed off-center in the flute, up to 1" from the edge of flute.
- Shear loads shall be applied flush with metal deck surface.
- Deck shall be 20-gauge minimum.
- Mechanical and plumbing design codes may prescribe lower allowable loads. Verify with local codes.
Metal Deck Insert: Shear Loads in Normal-Weight or Sand-Lightweight Concrete
over Metal Deck
- Allowable load must be the lesser of the concrete or rod strength.
- The allowable loads based on concrete strength are based on a factor of safety of 4.0.
- Allowable loads may not be increased for short-term loading due to wind or seismic forces.
- Anchors may be installed off-center in the flute, up to 1" from the edge of flute.
- Shear loads shall be applied flush with metal deck surface.
- Deck shall be 20-gauge minimum.
- Mechanical and plumbing design codes may prescribe lower allowable loads. Verify with local codes.
Typical Metal Deck Installation