Strong-Bolt® Wedge Anchor for Cracked and Uncracked Concrete

Tension Strength Design Data1

 
Shear Load Normal Weight Concrete Lightweight Concrete
Strong-Bolt Characteristic Shear Design Values
  1. The information presented in this table is to be used in conjunction with the design criteria of ACI 318 Appendix D, except as modified below.
  2. The value of φ applies when the load combinations of ACI 318 Section 9.2 are used. If the load combinations of ACI 318 Appendix C are used, refer to Section D4.5 to determine the appropriate value of φ. The 3⁄4 inch and 1 inch diameter are considered as a brittle steel element. The 1/2 inch and 5/8 inch diameters are considered as ductile steel elements.
  3. Pullout strength is not reported since concrete breakout controls.
  4. Adjust the characteristic pullout resistance for other concrete compressive strengths by multiplying the tabular value by (f'c,specified / 2,500)0.7.
  5. Adjust the characteristic pullout resistance for other concrete compressive strengths by multiplying the tabular value by (f'c,specified / 2,500)0.5.
  6. The value of φ applies when both the load combinations of ACI 318 Section 9.2 are used and the requirements of Section D4.4(c) for Condition B are met.If the load combinations of ACI 318 Appendix C are used, refer to Section D4.5 to determine the appropriate value of φ.
  7. The modification factor ψcp,N = 1.0 for cracked concrete. Otherwise,the modification actor for uncracked concrete without supplementary reinforcement to control splitting is either:
    1. ψcp,N = 1.0 if ca,min ≥ cac or 2. ψcp,N = Ca,min  ≥  1.5hef  if ca,min < cac
    Cac Cac
  8. The value of φ applies when both the load combinations of ACI 318 Section 9.2 are used and the requirements of Section D4.4(c) for Condition B are met. If the load combinations of ACI 318 Section 9.2 are used and the requirements of Section D4.4(c) for Condition A are met, refer to Section D4.4 to determine the appropriate value of φ. If the load combinations of ACI 318 Appendix C are used, refer to Section D4.5 to determine the appropriate value of φ.
  9. For sand-lightweight concrete, in lieu of ACI 318 Section D.3.4, modify the value of concrete breakout strength by 0.60. All-lightweight concrete is beyond the scope of this table.
  10. For sand-lightweight concrete, modify the value of Np,cr, Np,uncr and Neq by 0.60. All-lightweight concrete is beyond the scope of this table.

 

 