Titen HD® Threaded Rod Hanger for Cracked and Uncracked Concrete
Allowable Stress Design (ASD) Values for Titen HD® Rod Hanger
with 1/4" and 3/8" Shanks Tension Loads in Normal-Weight Concrete
- The allowable loads listed are based on a safety factor of 4.0.
- Allowable loads may not be increased for short-term loading due to wind or seismic forces.
- Refer to allowable load-adjustment factors for spacing and edge distance.
- The minimum concrete thickness is 1 1/2 times the embedment depth.
- Allowable load may be interpolated for concrete compressive strengths between 2000 psi and 4000 psi.