- The information presented in this table is to be used in conjunction with the design criteria of ACI 318 Appendix D, except as modified below.
- The tabulated value of φsa applies when the load combinations of Section 1605.2.1 of the IBC, or ACI 318 Section 9.2 are used and the requirements of ACI 318 D.4.4(c) for Condition B are met. If the load combinations of ACI 318 Appendix C are used, the appropriate value of φsa must be determined in accordance with ACI 318 D.4.5. Torq-Cutâ„¢ anchors are ductile steel elements as defined in ACI 318 D.1.
- The tabulated value of φcb applies when both the load combinations of Section 1605.2.1 of the IBC, or ACI 318 Section 9.2 are used and the requirements of ACI 318 Section D.4.4(c) for Condition B are met. Condition B applies where supplementary reinforcement is not provided. For installations where complying supplementary reinforcement can be verified, the φcb factors described in ACI 318 Section D.4.4 for Condition A are allowed. If the load combinations of ACI 318 Section 9.2 are used and the requirements of ACI 318 Section D.4.4 for Condition A are met, the appropriate value of φcb must be determined in accordance with ACI 318 Section D.4.4(c). If the load combinations of ACI 318 Appendix C are used, the appropriate value of φcb must be determined in accordance with ACI 318 Section D.4.5(c).
- The tabulated value of φcp applies when both the load combinations of IBC Section 1605.2.1 or ACI 318 Section 9.2 are used and the requirements of ACI 318 D.4.4(c) for Condition B are met. If the load combinations of ACI 318 Appendix C are used, the appropriate value of φcp must be determined in accordance with ACI 318 D.4.5(c).
- For sand-lightweight concrete, in lieu of ACI 318 Section D.3.4, modify the value of concrete breakout strength by 0.60. All-lightweight concrete is beyond the scope of this table.
- For the 2006 IBC, do replaces da.