The industry standard column cap. Precision factory gang-punched holes speed installation on this product line. Specifically designed to meet Canadian code requirements.

Material: CC3 1/4C, CC44C, CC46C, CC48C, CC64C, CC66C, CC68C, CC6-7 1/4C - 7 gauge; all others - 3 gauge

Finish: Simpson gray paint; may be ordered HDG; CCO - no finish.

Installation:

Options:


top Gallery:
  roll over images below to see larger image
 
CC CCOB CCO Optional CC with straps rotated 90°
  roll over images below to see larger image
 

There are cost-effective alternatives for replacing column caps by using a combination of connectors. Here are some examples. Designer must specify the options required.

NOTE: The side stirrup will be welded flush with the top of the main cap.

CCC

Instead of the column cap, consider this connector combination.

CC and WD
CCT
Instead of the column cap, consider this connector combination. CC and GLT
Side stirrups are available in different depths.

Order each connector separately. Specify all side stirrup widths and heights.
For more information, see Form T-CC and the Product Worksheet.


top Load Table:

This page for Canadian customers only.

Table
  1. Post sides are assumed to lie in the same vertical plane as the beam sides.
  2. Factored resistances may not be increased for short-term load duration.
  3. Factored resistances are determined using ΦFcp equal to: 812 psi (5.6 MPa)for D.Fir-L and 672 psi (4.64 MPa) for Spruce-Pine glulam sizes; 1092 psi (7.53 MPa) for SCL sizes; reduce where end grain bearing or buckling capacity of post governs.
  4. Factored uplift resistances have been increased 15% for earthquake or wind loading; reduce for other load durations in accordance with the code.
  5. Spliced conditions must be detailed by the specifier to transfer tension loads between spliced members by means other than the column cap.
  6. Factored uplift resistances do not apply to splice conditions.
  7. Specifier to design beam for factored uplift resistance based on effective shear depth as per 10.2.1.4 CSA O86-01.
  8. SCL assumes SG = 0.50.
  9. Beam depth must be greater than H1.

top
Catalog Pages (PDFs)
Order free catalogs by mail

Home | About Simpson | Contact Simpson | Browse Products | Product Use Information
Privacy Policy | User Agreement | Limited Warranty | Parent Company

Stay informed! Sign up for Simpson's newsletters

Copyright © 2009, Simpson Strong-Tie Company Inc. All Rights Reserved
Contact Webmaster with questions or comments.

Printed from
© 2009 Simpson Strong-Tie®