Wood Strong-Wall® Shearwalls: Installation of Raised-Floor Walls

  • Drilling or cutting holes in Wood Strong-Wall® is not allowed except as shown in Structural Details and the Allowable Hole Chart attached to each wall.
  • Typical shim thickness between the Strong-Wall and top plates or header is 7/8" or less using Simpson Strong-Tie® Strong-Drive® 1/4"x6" SDS Heavy- Duty Connector screws. For additional shim thickness, see detail 7/SW1.
  • For holdowns, per ASTM standards, anchor bolt nuts should be finger-tight plus 1/3 to 1/2 turn with a hand wrench, with consideration given to possible future wood shrinkage. Care should be taken to avoid over-torquing the nut, an impact wrench should not be used.
  • All raised-floor walls require 1 1/2" or 3" end distance from corner for end post bearing plate.
  • Subfloor must be cut out for end post bearing plates in raised-floor and 2nd-story installations. Additional bearing plates available for 1 1/8" subfloor.
  • Walls may also be used in 2x6 wall framing. Install the sheathing side at the exterior wall line and add furring to the interior framing side.
  • The SW-TUD1KT take-up device is recommended for 2nd-story installations in order to compensate for wood shrinkage and settlement due to dead load.
063a-2014
Raised-Floor Strong-Wall®: 1st-Story Installation

Caution: Drilling or cutting holes in Wood Strong-Wall® is not allowed except as shown in the Structural Details and the Allowable Hole Chart attached to each wall.

063b-2014
Raised-Floor Strong-Wall®: 2nd-Story Installation

See detail 3/SW2

U.S. Patents 6,006,487;
6,109,850; 6,327,831 and 6,643,986

063c-2014
Top-of-Wall Connection

See detail 6/SW1

063e-2014
Bottom-of-Wall Installation